WebDec 12, 2024 · The ratio of Voltage and Frequency is exactly the same (400/50 = 8.0, 480/60 = 8.0), so the motor will work at 480V 60Hz and provide it's full rated torque at nameplate FLA without issue. But the problem is with the load. Most likely your dust collection blower is a centrifugal type. http://www.50hz60hz.com/60hz-motor-running-on-50hz-power-supply.html
50Hz Operation 60Hz - Nidec
WebFeb 3, 2015 · The inductive reactance is higher at 60Hz, but the applied voltage is higher in direct proportion. As long as the load torque does not change between the two speeds (60Hz/50Hz), the motor will draw the same current at … WebMar 6, 2024 · Electrical machines designed for 50Hz can usually work safely in 60Hz power supply, but not applicable to 60Hz machines to be run in 50Hz power supply. It is not always easy to just change the machine or equipment to rated frequency considering the FINANCIAL BURDEN that comes with it. Can I use 50 Hz motor on 60Hz supply? phone repair shops motherwell
60Hz motor running on 50Hz power supply or vice versa
WebOct 27, 2024 · If saturation is more than 20% away at 60Hz, then you'll get away with it at 50Hz. If closer, then the core could saturate, drawing many times more current. You can avoid this by transforming the voltage … WebJun 17, 2012 · Example: A 60Hz 240Vac motor is going into 50Hz service. V/f = Y Hence: 240/60 = 4.0. So if Y x f = V then by plugging in the new frequency of 50 we see: 4.0 x 50 = V. V = 200. Running the motor at 200V at 50Hz will remove the V/f problem. Another way to think of this is: New voltage = Old voltage x 50/60. WebAug 23, 2009 · Also this 50 Hz motor will operate perfectly on a 60 Hz supply provided its supply voltage is stepped-up. 60 Hz/ 50 Hz = 6/5 * 100 = 120 %. Analysis 2: 60 Hz motor connected to 50 Hz supply: It is same as the above, but instead of stepping-up the supply voltage, it is necessary to step-down the supply voltage. 50Hz/ 60 Hz = 5/6 * 100 = 80 %. phone repair shops mansfield